Energy Measurement

For the CM and ESB modules there is fine-grained energy measurement in place using Megware's energy meters, attached to the respective compute nodes. In addition, the DCDB monitoring framework is deployed on the entire DEEP-EST prototype, providing a variety of sensor measurements in addition to energy consumption. There are different ways to get information about energy consumption for your jobs (and the nodes). Preferred methods are:

SLURM sacct command

This is probably the easiest way to get energy consumption for your interactive and batch jobs. Once your job has finished, you can use the sacct command to enquire the Slurm database about its energy consumption. For further information and an example on how to use the command for energy measurements, please see accounting.

Using DCDB

The "Data Center Data Base" (DCDB) stores measured values from node and infrastructure sensors at a high frequency (every 10 seconds), including power and energy consumption of the compute nodes. This allows for a very fine-grained analysis of consumed energy for your jobs, e.g. by specifying precise time-stamp ranges and by leveraging access to measured data from different components like CPU, GPU or memory, instead of using only single accumulated values. Hence, it offers a convenient way for analysis of SLURM jobs.

DCDB is currently deployed on the DEEP-EST prototype and it is continuously collecting sensor data. A total of 62595 sensors are available, each with a time-to-live of 1 year. Please refer to D5.4 for the full list of monitored sensors and further details about the DCDB deployment. The DCDB Gitlab ?repository is also a good source of documentation and usage examples. Two types of data are available:

DCDB is installed on the DEEP-EST deepv login node, from which data can be queried. To prepare the shell environment and expose the DCDB tools, please run the following:

source /opt/dcdb/dcdb.bash

At this point DCDB data can be queried using the dcdbquery and dcdbconfig tools. A distributed Cassandra instance is running on the dp-mngt01, dp-mngt02 and dp-mngt03 machines: only these three should be queried by the DCDB tools. By default, there is no need to be specify the target host, as the DCDB tools use a pre-defined value; in case you wish to explicitly select a host to be queried, you can do so with the -h option.

The dcdbconfig Tool

The dcdbconfig tool can be used to perform a variety of metadata-related actions. Running the following command will list all available actions:

dcdbconfig help

We will present the main dcdbconfig actions that can be of use to users. To print the complete list of sensors available to be queried on the prototype, run the following command:

dcdbconfig sensor list

To show the metadata for a specific sensor name, run the following command:

Template: dcdbconfig sensor show <SENSORNAME>
Example:  dcdbconfig sensor show /deepest/esb/s25/MemUsed

Sensor names are slash-separated strings structured like MQTT topics, where each segment indicates a level of the system (e.g., deepest system, esb module, s25 compute node). To show the list of jobs stored in the DCDB database, that are currently running on the prototype, run the following command:

dcdbconfig job running

To show the details of a specific job (e.g., node list, start time), run the following command:

Template: dcdbconfig job show <JOBID>
Example:  dcdbconfig job show 17435

A series of other actions to manage the sensor database are available, however users are advised not to use them so as not to alter the system?s behavior.

The dcdbquery Tool

The dcdbquery tool allows to perform sensor queries, returning results in CSV format. It requires a sensor name and a time range. To perform a basic query, run the following:

Template: dcdbquery <SENSORNAME> <TSTART> <TEND> 
Example:  dcdbquery /deepest/cn/s01/power now-5m now

Instead of a single sensor, a list of space-separated sensor names can be supplied as well; these will be queried sequentially. Instead of using relative time-stamps, absolute UNIX time-stamps (in s, ms, ns) as well as time/date strings can also be used:

Example: dcdbquery /deepest/cn/s01/power 1596543564693158000 1596543788812750000
         dcdbquery /deepest/cn/s01/power "2020-08-04 14:19:24" "2020-08-04 14:23:08"

Energy and Power Sensors

DCDB provides several types of energy and power measurements that can be useful for performance analysis. Depending on the data source, these can have different units and scales - this information can be shown by querying a sensor with the dcdbconfig sensor show command. In detail, these are the energy sensors available for compute nodes in the DEEP-EST prototype:

These, instead, are the available sensors for estimating power consumption:

In the case of multi-socket systems (i.e. CN and DAM), the pkg and dram energy and power sensors are available both for each single socket (e.g., under socket0/pkg-energy), as well as for the entire compute node. The same aggregation scheme applies for sensors associated with CPU performance counters. Aside from those on compute nodes, many other energy and power sensors are available on the DEEP-EST prototype: these are associated with the system's infrastructure and cooling equipment.

Using dcdbquery for Job Queries

DCDB collects a series of aggregated metrics for each job running on the system, every 30s. These can be queried using the same dcdbquery syntax as above. The sensor name, however, should be constructed as follows:

Template: dcdbquery /job<JOBID>/<SENSORNAME><STATNAME> <TSTART> <TEND> 
Example:  dcdbquery /job788354/pkg-energy.avg now-1h now

The <JOBID> field identifies the job to be queried. This matches with the job IDs reported by SLURM, and follows the same format of the latter for job packs and job arrays. For example, the following are valid queries:

Job Pack Example:  /job122444+1/pkg-energy.avg
Job Array Example: /job122999_15/pkg-energy.avg

In the job pack example above, data is queried for a specific sub-job in the pack. However, aggregated sensor data also exists for the pack as a whole, thus including measurements from multiple modules or allocations on the DEEP-EST prototype. This aggregated data can be queried using the base job ID of the pack, omitting the + notation. No high-level aggregation is performed across the different jobs of a job array.

The <SENSORNAME> field identifies instead the aggregated metric and can be one of the following:

Finally, the <STATNAME> field identifies the actual type of aggregation performed from the readings of the queried sensor, by combining the data of all compute nodes on which the job was running. It can be one of the following:

In order to get a cumulative measure of a job's performance (e.g., total energy spent or total amount of instructions computed), .sum should be used. The .avg and .med aggregations, on the other hand, indicate single-node performance in each 30s time window. It should be noted that, for a job to be measured by DCDB, its duration has to be longer than 30s. We currently expect to store job data for the entire lifetime of the system, and hence the time-to-live of 1 year does not apply to it.

BeeGFS Performance Metrics

DCDB also exposes a series of performance metrics associated with the BeeGFS distributed file system. Comprehensive documentation about the available metrics and their meaning is available ?here. All BeeGFS sensors in the DCDB database are identified by the /deepest/beegfs/ prefix, and they can be listed by using the following command:

dcdbconfig sensor list | grep beegfs

Most BeeGFS sensors do not directly map to users and compute nodes in the DEEP-EST prototype, and they require knowledge of the system's architecture to be interpreted.

Long-term Sub-sampled Sensor Data

The sensor data collected by DCDB (excluding per-job data) has a time-to-live of 1 year. After this interval the data will be automatically erased from the database. However, to keep track of the system?s history, DCDB automatically computes sub-sampled versions of all sensors. These are kept forever in the database, and can be queried as follows:

Template: dcdbquery ?<OPNAME>(<SENSORNAME>)? <TSTART> <TEND> 
Example:  dcdbquery ?.avg300(/deepest/cn/s01/power)? now-1h now

In this case, quoting is required to ensure proper parsing of the command in the shell. The <OPNAME> field defines the particular type of sub-sampling that is to be queried for the given sensor. The following alternatives are available:

DCDB computes sub-sampled versions of all sensors, with the exception of CPU core-level sensors (e.g., performance counters for specific CPU cores) and per-job sensors, to avoid inflating the size of the databases indefinitely. In general, the operations available for a DCDB sensor are shown along with its metadata when using the dcdbconfig sensor show command.

Grafana Visualization

A Grafana instance is also running and is reachable at grafanavm:3000. The grafanavm host is visible only from the prototype?s network, so ssh tunneling is required to reach it. In order to use Grafana, an account must be created: if you wish to have access, please contact Alessio Netti (alessio.netti@?) and one will be created for you. Normally, the Grafana instance should be already set up and you will not need to configure the DCDB data source. If that is not the case, please follow the instructions below.

Log into the Grafana web frontend and navigate into the Configuration->Data Sources menu. Here, click on Add Data Source and select DCDB. Please use the following values for the required fields in the configuration window of the DCDB data source:

URL: https://dp-mngt01:8081
Access: Server (Default)
User and Password: admin
Check "Basic Auth" and "Skip TLS Verify" under the "Auth" table 

At this point click on Save & Test once and, if the procedure was successful, you will be ready to add dashboards and panels using DCDB data.

Using /sys files

The energy meters provide their measured values through the "/sys" filesystem on the compute nodes using different files. To query the overall energy (in Joules) a node has consumed so far, you can use the energy_j file. You should integrate readings in your SLURM job script before and after you srun your commands to measure consumed energy by your commands (applications):

Unit=[Joules]

CM Module

srun sh -c 'if [ $SLURM_LOCALID == 0 ]; then echo ${SLURM_NODEID}: $(cat /sys/devices/platform/sem.5/energy_j); fi'

ESB Module

There are two energy meters present for the ESB nodes, one for the CPU blade and one for the GPU part:

srun sh -c 'if [ $SLURM_LOCALID == 0 ]; then echo ${SLURM_NODEID}: $(cat /sys/devices/platform/sem.1/energy_j); fi'
srun sh -c 'if [ $SLURM_LOCALID == 0 ]; then echo ${SLURM_NODEID}: $(cat /sys/devices/platform/sem.2/energy_j); fi'

To get the consumed energy by a multi-node job you have to accumulate all the values which makes it quite cumbersome, but for running on single nodes (maybe even in an interactive session) reading out current values directly from the files might be quite useful.